Floors, Interior - Tile over Structural Plank Subfloor
Areas of Application
Limitations
|
|
Legend
*** Essential
** Significant
* Helpful
Requirements
*** Essential
** Significant
* Helpful
Requirements
- maximum spacing of joists is 24" (610 mm) o.c.
- double layer wood floor consisting of:
- minimum structural plank subfloor thickness – 3/4" (19 mm)
- minimum underlayment thickness – 15/32", 1/2" nom. (13 mm)
Substrate Preparation
- verify that subfloor planks are properly fastened to framing members
- underlayment – minimum 15/32", 1/2" nom. (13 mm)-thick eposure 1, plugged-face plywood or OSB with 1/8" (3 mm) gap between sheets;
- any leveling of the assembly must be done prior to installing Schluter-DITRA
Movement Joints
- Schluter-DITRA does not eliminate the need for movement joints, including perimeter joints, within the tiled surface. Movement joints should be installed in accordance with industry standards and norms; see guidelines for the placement of movement joints for more details
Setting and Grouting Materials
- latex portland cement (p.c.) mortar - ANSI A118.11
- unmodified thin-set mortar - ANSI A118.1
- grout - ANSI A118.3, A118.6, A118.7, A118.8
Setting and Grouting Specifications
- tile - ANSI A108.5
- grout - ANSI A108.6, A108.9, A108.10
Other Considerations
- vapor barrier on crawl space floors according to regional building codes
- where a waterproof floor is required, all Schluter-DITRA seams and floor/wall transitions must be sealed with Schluter-KERDI-BAND using unmodified thin-set mortar; see waterproofing requirements for more details
- certain moisture-sensitive stones, e.g., green marble, or resin-backed tiles may require special setting materials. Consult stone supplier and Schluter®-Systems for more information

View Tile Assembly: