Floors, Interior - Tile over Structural Plank Subfloor

Areas of Application
  • over structural plank subfloors
  • interior dry or wet areas

Limitations

  • minimum 2" x 2" (50 mm x 50 mm) tile


 

Legend

*** Essential
**   Significant
*     Helpful


Requirements
  • maximum spacing of joists is 24" (610 mm) o.c.
  • double layer wood floor consisting of:
    - minimum structural plank subfloor thickness – 3/4" (19 mm)
    - minimum underlayment thickness – 15/32", 1/2" nom. (13 mm)

Substrate Preparation

  • verify that subfloor planks are properly fastened to framing members
  • underlayment – minimum 15/32", 1/2" nom. (13 mm)-thick eposure 1, plugged-face plywood or OSB with 1/8" (3 mm) gap between sheets;  
  • any leveling of the assembly must be done prior to installing Schluter-DITRA

Movement Joints

Setting and Grouting Materials

  • latex portland cement (p.c.) mortar - ANSI A118.11
  • unmodified thin-set mortar - ANSI A118.1
  • grout - ANSI A118.3, A118.6, A118.7, A118.8

Setting and Grouting Specifications

  • tile - ANSI A108.5
  • grout - ANSI A108.6, A108.9, A108.10

Other Considerations

  • vapor barrier on crawl space floors according to regional building codes
  • where a waterproof floor is required, all Schluter-DITRA seams and floor/wall transitions must be sealed with Schluter-KERDI-BAND using unmodified thin-set mortar; see waterproofing requirements for more details
  • certain moisture-sensitive stones, e.g., green marble, or resin-backed tiles may require special setting materials. Consult stone supplier and Schluter®-Systems for more information